CERTIFICATION

A representative organization leading the businesses of air cleaning
and environmental control industry

CA MARK

CA Mark

Clean Air Certification (CA Mark)
Clean Air Certification

CA MARK

CA mark is granted to the products which pass strict tests by certified test agencies in accordance with collective standards for indoor air clearner including dust collection efficiency, deodorization efficiency, noise, coverage and ozone concentration to provide reliable indoor air cleaners by the Korea Air Cleaning Association.


Purpose

It aims to bring the effects of consumer perception change as well as market expanding effects by granting organizational quality certification (CA: Clean Air Certification) to the product that passes strict performance test on the indoor air purifier and to protect consumers and to contribute to quality improvement of product by implementing autonomous quality control.


Scope of Application

It shall be applied to the safety and performance of air cleaner that is installed in a general house and office room to collect dust and deodorize odor.


Certification Criteria

INTORDUCE CA MARK

Certification Evaluation Criteria

  • Factory audit: Check whether the technical production conditions of the factory that manufactures the product meet the certification audit criteria
  • Product audit: Check whether the quality of the product meets the group standard certification criteria

1) Small Air Cleaner

Item Certification criteria
Unit Criteria
Mandatory Clean Air Delivery Rate
(CADR)
㎡/min Range 0.10 or more and less than 1.60
Criteria Display value 90% or more
Ozone concentration ppm less than 0.03
Noise level 7) Noise level performance criteria
Optional Fine dust reduction life mg Display value 90% or more
Noxious gas purification ability ㎡/min 6) Noxious gas purification ability and removal efficiency performance criteria
Noxious gas reduction life mg Display value 90% or more
Noxious gas removal efficiency % 6) Noxious gas purification ability and removal efficiency performance criteria
Fine dust sensor 8) Fine dust sensor performance criteria

2) Normal Air Cleaner

Item Certification criteria
Unit Criteria
Mandatory Clean Air Delivery Rate
(CADR)
㎡/min Range 1.6 or more and less than 15.0
Criteria Display value 90% or more
Noxious gas purification ability ㎡/min 6) Noxious gas purification ability and removal efficiency performance criteria
Ozone concentration ppm less than 0.03
Noise level 7) Noise level performance criteria
Optional Fine dust reduction life mg Display value 90% or more
Noxious gas removal efficiency % 6) Noxious gas purification ability and removal efficiency performance criteria
Noxious gas reduction life mg Display value 90% or more
Fine dust sensor 8) Fine dust sensor performance criteria

3) Medium Air Cleaner

Item Certification criteria
Unit Criteria
Mandatory Clean Air Delivery Rate
(CADR)
㎡/min Range 15.0 or more and less than 25.0
Criteria Display value 90% or more
Noxious gas purification ability ㎡/min 6) Noxious gas purification ability and removal efficiency performance criteria
Ozone concentration ppm less than 0.03
Noise level 7) Noise level performance criteria
Optional Fine dust reduction life mg Display value 90% or more
Noxious gas removal efficiency % 6) Noxious gas purification ability and removal efficiency performance criteria
Noxious gas reduction life mg Display value 90% or more
Fine dust sensor 8) Fine dust sensor performance criteria

4) Air Cleaner for Schools

Item Certification criteria
Unit Criteria
Mandatory Fine dust removal ability ㎡/min Range 15.0 or more and less than 25.0
Criteria Display value 90% or more
Ozone concentration ppm less than 0.03
Noise level dB(A) 7) Noise level performance criteria
Fine dust sensor 8) Fine dust sensor performance criteria
CO2 sensor additional functions - Submission of CO2 sensor test report
Homogeneity within 20% / Accuracy within 30%
Optional Fine dust reduction life mg Display value 90% or more
Noxious gas purification ability ㎡/min 6) Noxious gas purification ability and removal efficiency performance criteria
Noxious gas reduction life mg Display value 90% or more
Noxious gas removal efficiency % 6) Noxious gas purification ability and removal efficiency performance criteria

5) Large Air Cleaner

Item Certification criteria
Unit Criteria
Mandatory Fine dust removal ability ㎡/min Range 25.0 or more and less than 90.0
Criteria Display value 90% or more
Ozone concentration ppm less than 0.03
Noise level dB(A) 7) Noise level performance criteria

6) Noxious gas purification ability and removal efficiency performance criteria

 ① Noxious gas purification ability performance criteria

Noxious gas Criteria Note
Ammonia(NH3) Display value(average value) 40% or more ※ Performance criteria are applied compared to the average value displayed on the product.
Toluene(C7H8) Display value(average value) 40% or more
Formaldehyde(HCHO) Display value(average value) 40% or more
Average Display value(average value) 90% or more

 ② Noxious gas removal efficiency performance criteria

Noxious gas Criteria Note
Ammonia(NH3) Display value(average value) 40% or more -
Acetic acid(CH3COOH) Test result value 40% or more
Acetaldehyde(CH3CHO) Test result value 40% or more
Toluene(C7H8) Test result value 40% or more
Formaldehyde(HCHO) Test result value 40% or more
Average Test result value 70% or more

7) Noise level performance criteria

Range Criteria Note
Clean Air Delivery Rate
(㎡/min)
less than 4.0 less than 45.0 dB(A) ※ But, for air Cleaner for schools, 50.0 dB(A) or less
4.0 or more and less than 8.0 less than 50.0 dB(A)
8.0 or more and less than 16.0 less than 55.0 dB(A)
16.0 or more and less than 50.0 less than 60.0 dB(A)
50.0 or more and less than 75.0 less than 65.0 dB(A)
75.0 or more and less than 90.0 less than 70.0 dB(A)

8) Dust sensor performance criteria

Measurement performance
(%)
(Converted measurement weight of dust sensor / Fine dust measurement weight of the reference measuring instrument) x 100 or
(Particle number concentrations measured by dust sensor / Particle number concentrations measured by the reference measuring instrument) x 100
Certification criteria In the measurement range, Within 30% range at high concentration of reference measuring instrument and within 15 ㎍/㎥ at low concentration